Late last year we received reports of poor performance in the CWL-DV using the AFII 150 burner. We contacted R. W. Beckett and they did a re-application of this combination. If you have a customer that reports poor combustion such as pulsation, flutter, etc., please substitute the nozzle installed with the following Hago nozzles and settings.
Nozzles |
Pin # |
Air Setting |
|
CWL-85 |
.75 – 60°B Hago |
4 |
2 |
CWL-100 |
.85 – 60°B Hago |
4 |
3 |
CWL-110 |
1.0 – 60°B Hago |
6 |
4 |
This notice is only for the Beckett AFII 150 burner on the CWL-DV boiler only.
If there are any further question, please call for technical service at 570-385-0731.
Leave A Comment