In our ongoing effort to improve dependability and product performance we have changed the burner specifications for out “S” Series boiler to include 140 PSI pump pressure operation.
“S” Series Boiler/Burner Specification – Beckett Model “AFG” |
|||||
Boiler Size |
Pump Pressure |
Delavan Nozzle |
Air Shutter |
Air Band |
Burner Head |
S-85 |
140 PSI |
.65X80°B |
10* |
0 |
F-3 |
S-100 |
140 PSI |
.75X80°B |
8 |
0 |
F-3 |
S-110 |
140 PSI |
.85X80°B |
10 |
0 |
F-3 |
S-125 |
140 PSI |
1.00X80°B |
10 |
0 |
F-12 |
S-135 |
140 PSI |
1.10X80°B |
10 |
1 |
F-12 |
S-150 |
140 PSI |
1.25.X80°B |
10 |
2 |
F-12 |
* Low Firing Baffle Installed. |
The preceding table includes all the new pump pressure and nozzle data for a typical field operation. As in any good installation, the final burner settings should be made using the proper test equipment.